SMA Technologie AG Technical Data
Installation Guide SB40TL_50TL-IEN081211 13
Grid connection data
Nominal output power P
ACnom
4000 W 4600 W /
5000 W
b)
Max. output power P
AC, max
4000 W 5000 W
Nominal output current (at 230 V AC) I
ACnom
17.5 A 20 A
Max. output current I
AC, max
22 A 22 A
Harmonic distortion of output current
(at THD < 2 %,
P
AC
> 0.5
PACnom
)
K
IAC
< 4 %
Nominal AC voltage
Operating range
U
ACnom
U
AC
220 V, 230 V, 240 V
160 V - 280 V
b)
AC grid frequency (self-adjusting)
Operating range
f
ACnom
f
AC
50 Hz, 60 Hz
45 Hz - 65 Hz
b)
Power factor
(at nominal output power)
cos phi 1
Overvoltage category III
Test voltage (50 Hz) 1.4kV (1 s routine testing / 5 s type
testing)
Test surge voltage 4 kV (serial interface: 6 kV)
Operating consumption at night < 0.5 W
b) depending on country configuration
SB 4000TL-20 SB 5000TL-20