EasyManua.ls Logo

SMA SUNNY BOY 5000TL - Page 13

SMA SUNNY BOY 5000TL
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA Technologie AG Technical Data
Installation Guide SB40TL_50TL-IEN081211 13
Grid connection data
Nominal output power P
ACnom
4000 W 4600 W /
5000 W
b)
Max. output power P
AC, max
4000 W 5000 W
Nominal output current (at 230 V AC) I
ACnom
17.5 A 20 A
Max. output current I
AC, max
22 A 22 A
Harmonic distortion of output current
(at THD < 2 %,
P
AC
> 0.5
PACnom
)
K
IAC
< 4 %
Nominal AC voltage
Operating range
U
ACnom
U
AC
220 V, 230 V, 240 V
160 V - 280 V
b)
AC grid frequency (self-adjusting)
Operating range
f
ACnom
f
AC
50 Hz, 60 Hz
45 Hz - 65 Hz
b)
Power factor
(at nominal output power)
cos phi 1
Overvoltage category III
Test voltage (50 Hz) 1.4kV (1 s routine testing / 5 s type
testing)
Test surge voltage 4 kV (serial interface: 6 kV)
Operating consumption at night < 0.5 W
b) depending on country configuration
SB 4000TL-20 SB 5000TL-20

Related product manuals