If the Sunny Boy is not set for the installation country, set it using the two rotary switches as described
in section 6.4.2 „Setting Using a Rotary Switch” (Page 40).
You can also make the settings on a communication device using the "CntrySet“ parameter.
If you require parameter settings adjusted for your installation location, you can change them using
a communication device or copy settings to the Sunny Boy using an SD card.
3 0 DK5940E2.2* Italian no Italy
3 8 German no Italy
4 0 RD1663 Spanish yes Spain
4 8 PPC Greek no Greece
5 0 Kepco-guide* English no South Korea
5 8 G83/1* English no England
E 0 Off-Grid English no
E1 German no
E2 French no
E3 Spanish no
E4 Italian no
E 5 Greek no
F 0 SD-Card SD-Card no flexible
a)
Special setting: Parameter ACVtgRPro = 244 V instead of 253 V
b)
Special setting: Bluetooth transmission power reduced
(in accordance with French requirements)
*
)
Availability on request