SMA Sunny Boy 6000US - Fault Messages

SMA Sunny Boy 6000US
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA Solar Technology AG
78 SB50US-80US-IUS094030 Installation Guide
The installed firmware versions of the control system
processor (BFR) and the current regulator processor
(SRR) are displayed after 6 seconds.
Operation Messages
The LCD continuously scrolls through all relevant operating data. Each message (MSG) is displayed
for 5 seconds, after all messages have been displayed the LCD repeats from the beginning.
MSG #1 “E-Today“ (total energy produced on this day)
is displayed together with the current operating mode:
MSG #2 Nominal grid voltage configuration and actual
line-to-neutral voltage measurements:
The Sunny Boy 8000US may not be connected to a 208
V grid.
MSG #3 Actual AC power output and DC input voltage:
MSG #4 Accumulated energy yield of the device since
installation and the total operating hours:
Fault Messages
In case of a fault condition the LCD switches to “Fault“ mode and the backlight is activated.
The upper display line indicates one of the three following failure types:
•Disturbance
For example, this Disturbance message would be
displayed if the Sunny Boy detected a problem with
the frequency of the utility grid. The message would
clear automatically once the condition was
corrected. Disturbances are typically caused by a
measured value exceeding a predetermined limit.
The display will show the value of the error (at:) as
well as the present value for the particular
parameter (present:).
The screens may also be scrolled through manually by repeatedly knocking on the lid of
the inverter. Each knock advances the screen to the next message.