10.3 Specifications
10.3.1 Sunny Boy 5000US and Sunny Boy 6000US
SB 5000US SB 6000US
Inverter Technology True sine wave, low frequency tranformer
AC Operating Voltage
Range
183 - 229 (208 V nominal)
211 - 264 (240 V nominal)
244 - 305 (277 V nominal)
AC Operating
Frequency Range
59.3 - 60.5 (60 Hz nominal)
Peak Power Tracking
Voltage
250 - 480 V DC
Range of Input
Operating Voltage
250 - 600 V DC
Maximum DC Power 5300 W 6400 W
Maximum Array Input
Power (DC @ STC)
6250 W 7500 W
Maximum AC
Continuous Output
Power
5000 W 6000 W
Current THD Less than 4 %
Output Power Factor 0.95 - 1.0 (0.99 @ nominal conditions)
Peak Inverter Efficiency 96.8 % 97.0 %
CEC weighted
efficiency
95.5 % 95.5 % @ 208 V AC
95.5 % @ 240 V AC
96.0 % @ 277 V AC
Cooling OptiCool, forced active cooling
PV Start Voltage 300 V DC
Maximum AC
Continuous Output
Current
208 V = 24 A
240 V = 20.8 A
277 V = 18A
208 V = 29 A
240 V = 25 A
277 V = 21.6 A
Maximum DC Input
Current
21 A
25 A
Maximum input short
circuit current
36 A
Maximum utility
backfeed current to PV
array
50 A AC