Why is my SMA Inverter Sunny Island not connecting to the running generator?
- MMelissa KirbyAug 21, 2025
If your SMA Inverter Sunny Island isn't connecting to the running generator, several factors could be at play. First, check the generator's fuse. If that's fine, see if the power fed back into the generator during the permissible time has been exceeded, indicated by a "!" display, which blocks generator connection for a set time; in this case, set the "540.02 GnAck" parameter to Ackn. If the generator control relay (GnReq) is open, check if the generator was started manually and switch to autostart if needed. Lastly, if a GenMan is in use, verify the return signal (DigIn), as it allows only manual generator starts.