SMA Solar Technology AG STP60 SunSpec Modbus Profile – Assignment Tables
40197
Voltage, line conductor L2 to N (PPVphB), in V
V_SF
(40199) :
average value of all inverters
1 uint16 RO
40198
Voltage, line conductor L3 to N (PPVphC), in V
V_SF
(40199) :
average value of all inverters
1 uint16 RO
Scale factor voltage (V_SF): -1
Active power (W), in W
W_SF
(40201): sum of all inverters
Scale factor active power (W_SF): 2
Power frequency (Hz), in Hz
Hz_SF
(40203): Average value of
all inverters
1 uint16 RO
Scale factor power frequency (Hz_SF): -3
Apparent power (VA), in VA
VA_SF
(40205) sum of all invert-
Scale factor apparent power (VA_SF): 3
Reactive power (VAr), in var
VAr_SF
(40207) sum of all invert-
Scale factor reactive power (VAr_SF): 3
Displacement power factor cos φ (PF)
PF_SF
(40209): Average
value of all inverters
1 int16 RO
Scale factor displacement power factor (PF_SF): -2
Total yield (WH), in Wh
WH_SF
(40212): sum of all inverters
Scale factor total yield (WH_SF): 3
DC current (DCA), in A
DCA_SF
(40214): average value of all
inverters
Scale factor DC current (DCA_SF): -1
DC voltage (DCV), in A
DCV_SF
(40216): average value of all
Scale factor DC voltage (DCV_SF): -1
DC power (DCW), in W
DCW_SF
(40218): sum of all inverters
Scale factor DC power (DCW_SF): 2
Technical Information STP60-SunSpec_Modbus-TI-en-12 21