SMA Solar Technology AG STP60 SunSpec Modbus Profile – Assignment Tables
40352
Ramp-up time for change from current to new set value
(WMaxLimPct_RmpTms), in s: NaN
1 uint16 RO
40353
0 = Deactivated
1 = Activated
1 enum16
Set power factor to a certain value (OutPFSet)
OutPFSet_SF
(40368), (SMA: PF ref).
1 int16 RW
40355
Time period for change of the power factor
(OutPFSet_WinTms), in s: NaN
1 uint16 RO
40356
Permitted reaction time for change of the power factor
(OutPFSet_RvrtTms), in s: NaN
1 uint16 RO
40357
Ramp-up time for change from current to new set value
(OutPFSet_RmpTms), in s: NaN
1 uint16 RO
40358
Fixed power factor (OutPFSet_Ena), (SMA: Pfext):
Reactive power (VArWMaxPct), in % of WMax
VArPct_SF
(40369), (SMA: Qref).
1 int16 RW
40360
Reactive power (VArMaxPct), in % of VarMax
VArPct_SF
(40369):
NaN
1 int16 RO
40361
Reactive power (VArAvalPct), in % of VArAval
(40369):
NaN
1 int16 RO
40362
Time period for change of the apparent power limitation
(VArPct_WinTms), in s: NaN
1 uint16 RO
40363
Permitted reaction time for change of the apparent power
limitation (VArPct_RvrtTms), in s: NaN
1 uint16 RO
40364
Ramp-up time for change from current to new set value
(VArPct_RmpTms), in s: NaN
1 uint16 RO
40365
Mode of the percentile reactive power limitation (VArPct_Mod):
1 = in % of WMax
RO
Technical Information STP60-SunSpec_Modbus-TI-en-12 31