Sunny Boy 2500U Installation and Operator’s Manual
SB2500U-11:NE - 16 - SMA Regelsysteme GmbH
2.3.2 Connection to Electrical Utility Grid
The Sunny Boy must be connected to the grid with 3 cables
with two phases (L1) and (L2) and one equipment-grounding conduc-
tor(Protective earth (PE)).
WARNING: Make sure the main 240 V breaker in the main utility breake
r
box is switched OFF before you connect the AC terminal block.
The grid impedance value at the connection point should be as low as possible to
avoid an increase of the AC-voltage to non-permissible values while the Sunny Boy
feeds to the grid. This also results in a higher system efficiency.
EXAMPLE: The impedance is the sum of the electricity grid impedance at
house distribution and all impedance values of cables and clamping
points.
NB: Impedance values are
ca. 0.44 for a 70 feet (16.4 m) cable with a cross section of
AWG 14
ca. 0.40 for a 100 feet (33 m) cable with a cross section of
AWG 12
ca. 0.43 for a 175 feet (57 m) cable with a cross section of
AWG 10
The total impedance of the grid plus the interconnecting ac cables should be less
than 1.25 Ohm.