APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 36 of 62
No.
Items
Parameter
Default
Description
1
Adjust
Speed Type
(0-2)
2
0Not Used; 1Relay Adjust Speed
2GOV Adjust Speed
2
GOV Output
Reverse
(0-1)
0
0Disable1Enable.
3
GOV Center
Voltage SW1
(0-10.0)
0
Default central voltage: 0V
4
GOV Voltage
Range SW2
(0-10.0)
2.0
Default volt. range: (-2.5~+2.5)V
5
GOV Gain
(0-100)
20
GOV gain control
6
GOV
Stability
(0-100)
20
GOV stability control
7
Relay Adjust
Speed Dead
Band
(0-10.0)%
1.0
GOV relay control
8
GOV Relay
Gain
(0-100)%
10
9
GOV Relay
Stability
(0.05-1.60)s
0.10
10
GOV Relay
Response
(0.25-4.00)
0.5
Pump Unit Setting
1
Speed
Enabled
(0-1)
0
0Disable1Enable.
2
Flywheel
Teeth
(1-300)
118
Tooth number of the engine.
3
Rated Speed
(0-6000)RPM
500
Offer standard to judge over/under
speed.
4
Over Speed
Shut
(0-1000)%
114%
Setting value is percentage of rated
speed and delay value can be set.
5
Under
Speed Shut
(0-1000)%
80%
6
Over Speed
Warn
(0-1000)%
110%
Setting value is percentage of rated
speed. Delay value and return value
can be set.
7
Under
Speed Warn
(0-1000)%
86%