HGM400N Series Genset Controller User Manual Page 15 of 38
level sensor is open circuit and the action selects “Shutdown”, it will initiate
a shutdown alarm and the corresponding alarm information will be
displayed on LCD.
When the controller detects that config. sensor temperature (sensor type:
temperature sensor) has exceeded the pre-set value, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed
on LCD.
When the controller detects that config. sensor oil pressure (sensor type: oil
pressure sensor) has fallen below the pre-set value, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed
on LCD.
When the controller detects that config. sensor fuel level (sensor type:
level sensor) has fallen below the pre-set value, it will initiate a shutdown
alarm and the corresponding alarm information will be displayed on LCD.
When genset running time has exceeded the user setting maintenance time
and the action selects “Shutdown”, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD. The maintenance
alarm will reset if the action selects “Inactive”.
If over power detection is enabled, when the controller detects that the
power value (power is positive) has exceeded the pre-set value and the
action selects “Shutdown”, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.