HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 20 of 34
When the engine speed is
over than the point and hold
great than 2 seconds,
genset over shutdown
speed is active.
When genset frequency is
low than the point, genset
low frequency shutdown
and hold great than 10
seconds is active.
When genset frequency is
over than the point and hold
great than 2 seconds,
genset over shutdown
frequency is active.
High
temperature
shutdown
When engine temperature
sensor value is large than
this point and remain for 2
seconds, send out
shutdown alarm. When the
value is 140, send out
warning alarm. (It‟s suited
for engine temperature
sensor only).
Low oil
pressure
shutdown
When engine oil pressure
sensor value is less than
this point and remain for 2
seconds, send out
shutdown alarm. When the
value is zero, send out
warning alarm. (It‟s suited
for oil pressure sensor
only).
When low Fuel level sensor
value is less than this point
and remain for 10 seconds,
send out warning alarm.
When speed is zero and
remain for the delay, send
out shutdown alarm. When
the delay is zero, send out
warning alarm.