HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 23 of 34
Num
Parameter
Range
Default
Remark
P 50
(P45)
Switching
value output 3
set
(0-11)
5
Close Gens
P 51
(P46)
Switching
value output 4
set
(0-11)
6
Close mains (6010KC has
no function).
P 52
(P47)
Aux. input1
set
(0-10)
1
High Temperature alarm
switch input
P 53
(P48)
Aux. input 1
delay
(0-20.0)s
2.0
P 54
(P49)
Aux. input 2
set
(0-10)
2
Low oil pressure input
P 55
(P50)
Aux. input 2
delay
(0-20.0)s
2.0
P 56
(P51)
Aux. input 3
set
(0-10)
3
Auxiliary warning input
P 57
(P52)
Aux. input 3
delay
(0-20.0)s
2.0
P 58
(P53)
Aux. input 4
set
(0-10)
6
Oil engine closed state
input
P 59
(P54)
Aux. input 4
delay
(0-20.0)s
2.0
P 60
(P55)
Aux. input 5
set
(0-10)
10
Remote start input
P 61
(P56)
Aux. input 5
delay
(0-20.0)s
2.0
P 62
(P57)
Module power
on
(0-2)
0
0: Stop mode
1: Manual mode
2: Auto mode
P 63
(P58)
Module
address
(1-254)
1
P 64
(P59)
Passwords
set
(0-9999)
1234
P 65
(P60)
Crank
success
condition
select
(0-5)
2
Setting item is given in
Table 5.
P 66
(P61)
Speed
disconnect
(0-3000)RPM
360
When engine speed is large
than this point, starter will
disconnect.