HGM6100N Series Genset Controller User Manual Page 15 of 47
the current date is over the setting date and the maintenance action is
set as shutdown, controller sends warning alarm signal and it will be
displayed in LCD. Maintenance alarm can be reset by setting parameters
via passwords.
When external input is active, controller will send shutdown alarm signal
and it will be displayed in LCD.
If over power detection is enabled, when the controller detects that the
power value (power is positive) has exceeded the pre-set value and the
action selects “Shutdown”, it will initiate shutdown alarm.
If an error message is received from ECU via J1939, it will initiate
shutdown alarm.
If the module does not detect the ECU data, it will initiate shutdown
alarm.
When over current fault shutdown input is active, controller will send
shutdown alarm signal and it will be displayed in LCD.
Over Speed Shutdown
Input Alarm
When over speed shutdown input is active, controller will send shutdown
alarm signal and it will be displayed in LCD.
NOTE: ECU warning and Shutdown alarm explanation: check engine according to detailed alarm contents; otherwise
check engine user manual according to SPN alarm code for gaining information.