EasyManua.ls Logo

SMC Networks EX600-ED Series - Page 57

Default Icon
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-57-
No. DOC1045423
Digital Input/Output unit parameters (continued)
No.
Parameter
Definition
Item
Content
Default
setting
Parameter
setting range
10
Monitor input
or output
ON/OFF
counter limit
Generates error
when the operation
count exceeds the
set limit value.
4
Enable
Generates an error.
Limit value: 1 to 65000
5
Channel
Disable
Does not generate an
error.
11
Input or Output
ON/OFF
counter clear
6
Clears the Input or
Output ON/OFF
counter to zero.
-
-
-
-
1: Could be incorrectly recognized as short circuit depending on used load (e.g.: lamp load). If detection is incorrect, disable the
parameter setting.
2: This function is valid only when “Hold/Clear priority setting” of the system parameter (page 51) is set to “Via software”.
3: Some PLC does not support an idle mode.
4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
5: Times for setting is set value × 1000 times.
6: Refer to “Counter value” of Index 50x3:0 in the CoE object dictionary (page 110) or the Web server (page 121) for the clear method.

Related product manuals