-36-
EX※※-OMR1012
•Digital input unit parameters
Parameter
setting
No. Parameter Definition Item Content
Default
setting
By
E.O.
By
W.S.
Enable Generates an error.
○
1
The power
supply short
circuit
detection for
control and
input
Generates error
per unit when the
short circuit of the
power supply for
the input device is
detected.
Disable
Does not generate an
error.
○ ○
Enable Generates an error.
2
Open circuit
detection
1
Generates error
per channel when
the disconnection
of the input device
is detected.
2
Disable
Does not generate an
error.
○
○ ○
Enable Ignores inrush current.
3
Inrush current
filter
Selects per unit the
over current
detection for
100 msec after
supplying power.
Disable
Does not ignore inrush
current.
○
○ ○
0.1 ms
1.0 ms
10 ms
4
Input filtering
time
Sets the time to
ignore the input
signal change per
unit.
20 ms
Selects the time for
filtering.
1.0 ms
○ ○
1.0ms
15 ms
100 ms
5
Input
extension
time
Sets the time to
hold the input
signal per unit.
200 ms
Selects the time to hold
the input signal.
15 ms
○ ○
Enable
Generates an error.
Val: 1 to 65000
4
6
Channel
ON/OFF
counter
Memorizes the
number of times
the input device is
ON. Generates
error per channel
when the operation
count exceeds the
set value.
3
Disable
Does not generate an
error.
○
○ ○
7
Valve
ON/OFF
counter clear
Clears the valve
ON/OFF counter to
0. (Refer to page
77 for the clear
method).
-
- -
x
○
1: Disconnection detection is a function only available for digital unit (EX600-DXPC1, EX600-DXNC1) with disconnection detection.
2: 2-wire type input equipment cannot be correctly detected if its leakage current is 0.5 mA or less while the equipment is in the OFF state
(reed sensor, etc.).
Ensure that all input equipment used has a leakage current above 0.5 mA in the OFF state.
3-wire type input equipment cannot be correctly detected if its current consumption is 0.5 mA or less.
The open circuit of input signals cannot be detected.
3: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
4: Times for setting is set value x1000 times.