10 Troubleshooting Continued
Internal temp.
sensor
High temp.
failure
Internal temp. sensor
value exceeds the high
temp. cutoff
temperature.
Check the set value for high
temp. cutoff temperature and
confirm the temperature really
reaches this value.
Flow rate of circulating
fluid is zero.
If the flow rate of the circulating
fluid is zero, the temperature of
circulating fluid can’t be
detected and might increase.
Confirm the flow of circulating
fluid is not stopped by valves
etc.
Internal
temp. sensor
Low temp.
failure
Internal temp. sensor
value is lower than low
temp. cutoff
temperature.
Check the set value for low temp.
cutoff temp. and confirm the
temperature really reaches this
value.
Flow rate of circulating
fluid is zero.
If the flow rate of the circulating
fluid is zero, the temperature of
circulating fluid can’t be
detected and might decrease.
Confirm the flow of circulating
fluid is not stopped by valves
etc.
Facility water temp is
high.
Decrease facility water temp. and
increase a flow rate.
If flow rate of circulating fluid is
zero, the temperature of
circulating fluid cannot be
measured and the temperature
of heat exchanger may
increase. Ensure the circulating
fluid is allowed to flow.
Cooling or heating
capacity overload.
No temperature decrease when
100% cooling output.
No temperature increase when
100% heating output.
Volume of circulating
fluid is too large.
If the volume of circulating fluid
system is too large, the change
of temperature takes a long
time. In this case, change
overload judging time setting to
avoid this alarm. (Refer to 6.3.2)
Low circulating
flow rate alarm
(Option)
The flow rate of the
circulating fluid is 1
L/min. or less
Investigate why the flow rate
of the circulating fluid is low
and take countermeasures.
Internal
temp. sensor
disconnectio
n alarm
High level noise
entered the temp.
sensor line.
Check whether unstable
temperature is caused by
noise. Please consult SMC if it
is caused by noise.
External
temp. sensor
disconnectio
n alarm
The external temp.
sensor is not
mounted.
For learning control or
external tune control, be sure
to mount the external temp.
sensor.
Abnormal auto
tuning alarm
Capacity of
circulating fluid is too
large.
Adjust PID value (proportional
band, integral time and
derivative time) of setting
mode Level 2 by hand.
Overloaded during
auto tuning mode
Fluid level of tank is
not enough.
Check all fluid connections
connected with the product.
Temperature rises and
falls +/-1 to 2 C
gradually about the set
point temperature.
Flow rate of
circulating fluid is
low.
Keep the flow rate 3L/min or
more.
PID parameters are
set incorrectly.
If the temperature cannot be
stable at default value,
perform auto tuning.
11 Declaration of Conformity
Below is a sample Declaration of Conformity(DoC) used for this product.
An actual DoC will be supplied with each product.
http// www.smcworld.com (Global) http// www.smceu.com (Europe)
Specifications are subject to change without prior notice from the manufacturer.
© 2017 SMC Corporation All Rights Reserved.