Details of Communication Format
HECR 4-4
<Specifying unit>
Host →
Data (D2, D2, D3) changes following bit line to ASCII code. (1 is for ON, 0 is for OFF)
High temp. cut off alarm ERR12
Low temp. cut off alarm ERR13
Output failure alarm ERR15
Upper temperature limit alarm WRN
Lower temperature limit alarm WRN
DC power supply failure alarm ERR11
External sensor failure alarm ERR18
Internal sensor failure alarm ERR17
During Auto tuning or auto tuning warning ERR19
Flow switch alarm ERR16 or level switch alarm ERR20
When some alarms/warnings go off at the same time, D1 to D3 reaches the added value.
Ex. When the “Upper temperature limit alarm” and the “DC power voltage alarm” go off simultaneously,
D2 will be 23X1+22X0+21X0+20X1=9(=39H).