Check to make sure the air ducting is not restricted.
Check to make sure the combustion air intake pipe and the
exhaust are not crushed or plugged.
Check the Glow Pin Screen and Replace if Dirty.
To reset the system:press the “OFF” button → wait for 15 minutes, this should clear the error codes, then
turn ON the system. If the system does not clear the code, disconnect battery power by removing the main
heater fuse at the battery for 5 minutes or more, then reinsert the main fuse and turn the system ON.
Maintenance Instructions
Switch the heater ON at least once a month for about 10 minutes, even if there is no need for heat.
Check the opening of the combustion air supply and the exhaust system after longer standstill periods;
clean if necessary.
Before the heating period starts the heater should undergo a trial run. If persistent extreme smoke,
unusual burning noises or unburned fuels smell develop or if electric / electronic parts heat up, the heater
shall be switched off immediately. Remove fuse or disconnect battery power.
At least once a year the heater should be inspected and maintained as follows;
Remove the glow pin using the special socket tool. Inspect the glow pin for any damage to wires or
wire connections and scratches or buildup on the heating element. Wipe the glow pin clean with a
soft cloth only, do not use anything abrasive to clean the glow pin. If the glow pin shows any signs
of wear or damage it must be replaced.
Remove the atomizer screen with a hook-pick or pick and needle nose pliers. The atomizer screen
cannot be reused and must be replaced annually.
Inspect the atomizer screen chamber for buildup and clean with a small wire brush and vacuum out
debris if required. Confirm the small air inlet hole on the side of the atomizer screen chamber is not
obstructed with debris or buildup.