MAINTENANCE ALARMS CONFIG – Allows the service (maintenance password required) to set up to 6 alarms of different
or the same type.
The alarms congured in this menu will be visible on the maintenance dashboard.
The alarm ID will be shown in the product logs if this alarm is activated, to activate the alarm rst change "STATUS" to
"ENABLED", user will then have access to other conguration parameters.
Possible alarm conguration:
ALARM
TYPE
ALARM NAME DESCRIPTION
THRESHOLD
UNIT
"THRESHHOLD
DEFAULT
VALUE"
"UPPER
THRESHOLD
MAX. VALUE"
1
CYCLE EXC.
"Maximum number of switching cycles.
A cycle is when the switch has reached the
oposite source and transferred back once (for
example I-off, off-2, 2-off, off-1)"
number of cycles 5000 10 000
2
OPERATION EXC.
Maximum number of operation (any change
of position order including off position)
number of
operations
10 000 10 000
3
GENSET RUNTIME S1
"Total amount of time that the genset 1 has
been working (supplying or not the load). Can
be used
for genset maintenance purposes."
hours 250 400 000
4
GENSET RUNTIME S2
"Total amount of time that the genset 2 has
been working (supplying or not the load). Can
be used
for genset maintenance purposes."
hours 250 400 000
5
TOT GS1 TIME ON
LOAD
Total amount of time that the genset 1 has
been connected to the load. Can be used for
genset maintenance purposes.
hours 250 400 000
6
TOT GS2 TIME ON
LOAD
Total amount of time that the genset 2 has
been connected to the load. Can be used for
genset maintenance purposes.
hours 250 400 000
7
INSPECTION
"Counts the time after the last inspection
(entered in “Inspection Mode” of the
maintenance menu). Can be
used for periodic inspection/service purposes
on the A TS. By default it is set to 300
months which is the maximum valu e.
Socomec recommends 12 months after
servicing."
Months 300 300
8
CONNECTED
Maximum number of time the input
CONNECTED has been switched on
action 3 10 000
9
WITHDRAWN
Maximum number of time the input
WITHDRAWN has been switched on
action 3 10 000
10
TOTAL TRIP BRK1
Maximum of time the input TRIP BRK1 has
been switched on
action 3 10 000
11
TOTAL TRIP BRK2
Maximum of time the input TRIP BRK2 has
been switched on
action 3 10 000