ATYS D10 / D20 - 542359B - SOCOMEC
5.2.1. Programming example
Load shedding conguration: LS
LS variable allows programming the timer associated shedding.
OUT-
PUT
Function Setting range Default values
01 to n LS 0 to 60 s (≤DTT)* 2
* In case the DTT variable conguration value is below the LS, value LS will be automatically set to the DTT value.
fonction
temporisation associée
Step 1: Press "right" push button to make
the first variable blink
Step 2: press "up" and "down" to
modify the variable
Step 3: Press "validate" to validate the
variable
Step 4: Press "down" to access the nO
selection
function
timer