ITYS 1-3 kVA - 551430A - SOCOMEC
39
EN
MODEL NAME
ITY3-
TW010B
ITY3-
TW010LB
ITY3-
TW020B
ITY3-
TW020LB
ITY3-
TW030B
ITY3-
TW030LB
Power rating VA/Watt 1000VA/1000W 2000VA/2000W 3000VA/3000W
Efficiency
Line mode 89% 93%
ECO mode 96% 97%
Input
performance
Voltage range 160-300V 100% load, 110-160V derating to 50% load linearly
Frequency range
Full range: 40Hz-70Hz
(1)
Normal mode: 45Hz-55Hz for 50Hz, 54Hz-66Hz for 60Hz
(1)
PF >0.99
THDI <5%
Output
performance
Rated voltage 200/208/220/230/240 VAC (derating 10% at 208V, derating 20% at 200V)
PF PF = 1
Voltage accuracy ±1%
THDv <1% linear load; <5% nonlinear load
Transfer time
(Typical)
0ms@ line <-> battery; 4ms @ line <-> bypass; 10ms @ ECO <->Inverter
Crest ratio 3:1
Overload
(Line mode)
100%<load≤105% continuous.
105%< load ≤125% for 5 minutes
125<load≤150% for 30 seconds.
>150% for 500ms.
Overload
(Battery mode)
100%<load≤105% continuous.
105%< load ≤125% for 2 minutes
125<load≤150% for 10 seconds.
>150% for 500ms.
Output
connection
Socket (IEC) 4 x IEC C13 8 x IEC C13
8 x IEC C13
1x IEC C19
8 x IEC C13
1x Terminal
Socket (Tower AU) 2 x AU 4 x AU + 1 x IEC C19
Battery
Voltage 36VDC 36VDC 72VDC 72VDC 72VDC 72VDC
Capacity (AH) 7Ah - 9Ah - 9Ah -
Maximum EBM quantity 4
Charger
Charging method Optimize battery management
Charging current 1.5A 8A 1.5A 8A 1.5A 8A
Recharging time 3h to 90% NA 3h to 90% NA 3h to 90% NA
Other mode CVCF Derating to 60%
Physical
performance
Dimensions
(W*D*H) MM
145*404*224 192*428*322
IP protection level IP20
Environment
Operating
temperature
0-45°C, 40-45°C load derating to 80%
and Max battery charger current 4A
Relative humidity 0-95%
Altitude 0~3000m (derating 1 % every up 100m @1000~3000m)
Acoustic noise <45dB at front 1m <50dB at front 1m
Certification EN IEC 62040-1 / EN IEC 62040-2 (C2 category) / AS 62040-1 / AS 62040-2
Performance EN IEC 62040-3
Manufacture ISO 9001:2015 / ISO 14001:2015
(1) In free running mode and in converter mode, UPS needs to be de-rated to 60% capacity (rated output power and maximum
charging current).