31EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
ITYS PRO ALARMS
Address Bits Acronym Description
0x003B
b00 A048 Bypass Critical Alarm
BYPASS
b01 A049 Bypass Preventive Alarm
b02 A050 Bypass Input Supply not OK
b03 A051 Phase Rotation fault
b04 A052
b05 A053 Transformer Alarm
b06 A054 Fan failure
b07 A055 ACS Alarm
ENVIRONMENT
b08 A056
b09 A057
b10 A058
b11 A059 UPS Power OFF
b12 A060 Wrong Configuration
INTERNAL
b13 A061 Internal / Communication failure
b14 A062 Option Board Alarm
b15 A063