Connection to the mains power supply and to the load(s) must be made using cables of suitable cross section, in accordance with
current standards.
If not already provided, install a PDU panel allowing isolation of the mains supply upstream of the UPS. The panel must be equipped
with an automatic switch rated high enough to handle the current draw on full load, and with a residual current device.
If requested, the UPS can also be switched off utilizing a remote external shutdown contact.
The command is acknowledged when the contact is made and held for 3 seconds (default),
whereas the external contact must be made between the common and input pins.
The external contact MUST be dedicated and voltage-free, so as not to cause
permanent damage to the UPS.
4. CONNECTIONS
1100 VA 3000 VA1700 VA
2200 VA