5000 - 7000 - 9000 - 11000 VA
NETYS RT
INSTALLATION AND OPERATING MANUAL EN
www.socomec.com/netys-manuals

Questions and Answers

  • D
    Daniel TurnerSep 3, 2025
    What to do if socomec NETYS RT 5000 VA UPS shows INV Volt Abnormal?
    • P
      penarichardSep 3, 2025
      If the Socomec UPS displays 'INV Volt Abnormal', this indicates an internal fault. Contact service personnel.
  • J
    James HolmesSep 18, 2025
    What causes overtemperature in socomec NETYS RT 5000 VA UPS?
    • M
      Michael BowenSep 18, 2025
      Overtemperature in your Socomec UPS can be caused by: * Obstructed air intake fans or fan cowl. Select a well-ventilated area for the UPS to allow proper heat dissipation. * Ambient temperature exceeding 40 °C (104 °F). Place the UPS in a cooler location.
  • S
    Stacey MayerSep 16, 2025
    How to fix faulty communication between PC and socomec NETYS RT 5000 VA UPS?
    • C
      Carl GreenSep 16, 2025
      To troubleshoot faulty communication between your PC and Socomec UPS: * Check the transmission speed and try changing it. * Verify the RS232 connection, referring to the "Communication" section of this manual, and reconnect the UPS to the COM1/COM2 port of the PC. * Ensure the USB connection is correct by reconnecting the UPS to the USB port of the PC.
  • C
    courtney62Sep 14, 2025
    What does it mean when the "Replace battery" LED is lit on my socomec UPS?
    • D
      Daniel MeyerSep 14, 2025
      If the "Replace battery" LED is lit on your Socomec UPS, it indicates that the batteries may be flat. Try charging the batteries for a minimum of 8 hours.
  • R
    Robin SanchezSep 12, 2025
    Why is the "Overload" LED lit on my socomec NETYS RT 5000 VA UPS?
    • S
      Stephanie LindseySep 12, 2025
      If the "Overload" LED is lit on your Socomec UPS and a continuous alarm is sounding, it indicates an overload condition. To resolve this, disconnect non-essential loads from the UPS.
  • S
    Stacy CruzSep 12, 2025
    What to do if socomec UPS does not guarantee the expected backup time?
    • A
      Alan RobertsonSep 12, 2025
      If your Socomec UPS isn't providing the expected backup time, consider the following: * The internal batteries might not be fully charged. Recharge them for at least 8 hours. * The UPS could be overloaded. Disconnect any non-essential loads.
  • A
    Angela McintyreSep 9, 2025
    What to do if my socomec NETYS RT 5000 VA does not power up?
    • H
      Hector JacksonSep 9, 2025
      If your Socomec UPS is not powering up (no alarm, no LEDs), here are a few things to check: * Ensure the ON/TEST button has been pressed to switch the UPS on. * If there was a shutdown due to a flat battery and no mains power, wait for the mains power to be restored. * Check if the thermal-magnetic switch on the rear panel has tripped. If so, reduce the load connected to the UPS, then reset the switch.
  • K
    Katherine TurnerSep 7, 2025
    What to do if my socomec NETYS RT 5000 VA UPS is in "Battery Mode" even with mains connected?
    • M
      Maria MannSep 7, 2025
      If your Socomec UPS is running in battery mode despite a healthy mains connection, it could be due to several reasons: * The input voltage may not be registering at the UPS input. Check the input voltage connection. * The thermal-magnetic switch on the rear panel might have tripped. Reduce the load and reset the switch. * The input voltage could be too high, too low, or distorted. In this case, have the mains voltage checked by a qualified electrician.
  • B
    Bryan EspinozaSep 5, 2025
    What to do if socomec UPS shows Charger Fault?
    • K
      Kimberly Meyers PhDSep 5, 2025
      If your Socomec UPS displays a 'Charger Fault', it means the UPS has an internal fault. Contact service personnel.
  • S
    Sherry DavenportAug 20, 2025
    What to do if socomec NETYS RT 5000 VA UPS shows output overload shutdown?
    • W
      wwalshAug 20, 2025
      If your Socomec UPS is showing an output overload shutdown, it means the UPS is overloaded. You should check the power consumption of the connected loads and remove any unnecessary ones to reduce the load on the UPS.

socomec NETYS RT 5000 VA Specifications

General IconGeneral
Power Rating5000 VA
Active Power4500 W
Input Voltage230 V
Output Power Factor0.9
Form FactorTower
Output Voltage230 V
Frequency Range40 - 70 Hz
Efficiency≥ 95%
Battery TypeLead-acid
Communication InterfaceRS232, USB
Operating Temperature0 °C to 40 °C
ProtectionOverload, short circuit, over temperature
Output Power5000 VA / 4500 W