What to do if socomec UPS shows INV Volt Abnormal?
- JJade VillaSep 4, 2025
If the Socomec UPS displays 'INV Volt Abnormal', this indicates an internal fault. Contact service personnel.

What to do if socomec UPS shows INV Volt Abnormal?
If the Socomec UPS displays 'INV Volt Abnormal', this indicates an internal fault. Contact service personnel.
What causes overtemperature in socomec NETYS RT 5000?
Overtemperature in your Socomec UPS can be caused by: * Obstructed air intake fans or fan cowl. Select a well-ventilated area for the UPS to allow proper heat dissipation. * Ambient temperature exceeding 40 °C (104 °F). Place the UPS in a cooler location.
How to fix faulty communication between PC and socomec NETYS RT 5000 UPS?
To troubleshoot faulty communication between your PC and Socomec UPS: * Check the transmission speed and try changing it. * Verify the RS232 connection, referring to the "Communication" section of this manual, and reconnect the UPS to the COM1/COM2 port of the PC. * Ensure the USB connection is correct by reconnecting the UPS to the USB port of the PC.
What does it mean when the "Replace battery" LED is lit on my socomec UPS?
If the "Replace battery" LED is lit on your Socomec UPS, it indicates that the batteries may be flat. Try charging the batteries for a minimum of 8 hours.
Why is the "Overload" LED lit on my socomec NETYS RT 5000?
If the "Overload" LED is lit on your Socomec UPS and a continuous alarm is sounding, it indicates an overload condition. To resolve this, disconnect non-essential loads from the UPS.
What to do if socomec NETYS RT 5000 UPS does not guarantee the expected backup time?
If your Socomec UPS isn't providing the expected backup time, consider the following: * The internal batteries might not be fully charged. Recharge them for at least 8 hours. * The UPS could be overloaded. Disconnect any non-essential loads.
What to do if my socomec NETYS RT 5000 does not power up?
If your Socomec UPS is not powering up (no alarm, no LEDs), here are a few things to check: * Ensure the ON/TEST button has been pressed to switch the UPS on. * If there was a shutdown due to a flat battery and no mains power, wait for the mains power to be restored. * Check if the thermal-magnetic switch on the rear panel has tripped. If so, reduce the load connected to the UPS, then reset the switch.
What to do if my socomec NETYS RT 5000 is in "Battery Mode" even with mains connected?
If your Socomec UPS is running in battery mode despite a healthy mains connection, it could be due to several reasons: * The input voltage may not be registering at the UPS input. Check the input voltage connection. * The thermal-magnetic switch on the rear panel might have tripped. Reduce the load and reset the switch. * The input voltage could be too high, too low, or distorted. In this case, have the mains voltage checked by a qualified electrician.
What to do if socomec NETYS RT 5000 shows Charger Fault?
If your Socomec UPS displays a 'Charger Fault', it means the UPS has an internal fault. Contact service personnel.
What to do if socomec NETYS RT 5000 shows output overload shutdown?
If your Socomec UPS is showing an output overload shutdown, it means the UPS is overloaded. You should check the power consumption of the connected loads and remove any unnecessary ones to reduce the load on the UPS.
| Category | UPS |
|---|---|
| Model | NETYS RT 5000 |
| Output Power | 4500 W |
| Input Voltage | 230 V |
| Relative Humidity | 0 - 95 % non-condensing |
| Weight | 22 kg |
| Power Rating | 5000 VA |
| Output Frequency | 50/60 Hz |
| Topology | Double Conversion Online |
| Output Waveform | Sinewave |
| Battery Type | Sealed Lead-Acid (VRLA) |
| Typical Backup Time at Full Load | 5 minutes |
| Communication Interfaces | RS232, USB, SmartSlot for expansion cards |
| Display | LCD |
| Operating Temperature | 0 °C to +40 °C |
| Form Factor | Tower |
| Standards Compliance | IEC 62040 |