NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
48
EN
Press and hold the button for 3 seconds
and release it after you hear one beep.
In Progress...
Self Diagnosis
BYPS
231 V
PS
BAT T
999 min
4
Once the UPS runs normally, switch on the output protective device (see Figure
7-3) installed between the UPS and the loads.
To prevent the UPS from activating the overload protection mechanism
during the start-up process, please turn on the high-power loads rst and
then the low-power loads.
8.2. Single Unit Turn-off
1
Make sure all of the loads connected to the UPS are off.
2
(1) Press and hold the ON/ OFF button (
) for 3 seconds, (2) release it after
you hear one beep, (3) use the Scrolling Up or Down button ( / ) to select
'Yes', and (4) press the Enter button ( ) to conrm your selection.
3
Switch off the input breaker, input protective device (see Figure 7-3) and output
protective devices (see Figure 7-3).
4
After the LCD backlight goes dim and the fans stop completely, switch off the
battery breaker to ensure that there is no remaining battery power.