EasyManua.ls Logo

socomec NETYS RT 5000 - Single Unit Turn-Off

socomec NETYS RT 5000
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
48
EN
Press and hold the button for 3 seconds
and release it after you hear one beep.
In Progress...
Self Diagnosis
BYPS
231 V
PS
BAT T
999 min
4
Once the UPS runs normally, switch on the output protective device (see Figure
7-3) installed between the UPS and the loads.
To prevent the UPS from activating the overload protection mechanism
during the start-up process, please turn on the high-power loads rst and
then the low-power loads.
8.2. Single Unit Turn-off
1
Make sure all of the loads connected to the UPS are off.
2
(1) Press and hold the ON/ OFF button (
) for 3 seconds, (2) release it after
you hear one beep, (3) use the Scrolling Up or Down button ( / ) to select
'Yes', and (4) press the Enter button ( ) to conrm your selection.
3
Switch off the input breaker, input protective device (see Figure 7-3) and output
protective devices (see Figure 7-3).
4
After the LCD backlight goes dim and the fans stop completely, switch off the
battery breaker to ensure that there is no remaining battery power.

Related product manuals