EasyManua.ls Logo

Sofar 1100TL - User Manual

Sofar 1100TL
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Shenzhen SOFARSOLAR CO., Ltd.
User manual
Solar Grid-tied Inverter
Product Model:
SOFAR
1.1K~3KTL

Questions and Answers

  • C
    curryamyAug 18, 2025
    What to do if my Sofar 1100TL Inverter shows a GridOVP error frequently?
    • A
      Ashley CameronAug 18, 2025
      If the Sofar Inverter's grid voltage or frequency is frequently abnormal, verify that the grid voltage and frequency are within the acceptable range. If not, contact technical support. If they are within range, inspect the AC circuit breaker and AC wiring. If the grid voltage/frequency is within the acceptable range and AC wiring is correct, but the alarm persists, contact technical support to adjust the grid over-voltage, under-voltage, over-frequency, and under-frequency protection points after getting approval from the local electrical grid operator. However, if the alarm occurs occasionally, it might be due to occasional abnormalities in the electric grid. The inverter should automatically return to normal when the grid stabilizes.
  • J
    Jeffrey GuzmanAug 20, 2025
    What to do if my Sofar Inverter displays a GFCIFault error?
    • C
      Christina DelacruzAug 20, 2025
      If the GFCIFault occurs occasionally on your Sofar Inverter, it may be due to temporary external circuit issues. The inverter should automatically return to normal once the fault is resolved. However, if the fault occurs frequently and persists, check the insulation resistance between the PV array and earth (ground) to ensure it is not too low. Also, inspect the insulation conditions of the PV cable.
  • E
    evan76Aug 23, 2025
    Why does my Sofar 1100TL show a BusUVP error?
    • D
      Dylan BarkerAug 23, 2025
      If your Sofar Inverter displays a BusUVP error, and the PV array configuration is correct, it is possible that the solar irradiance is too low. The inverter should automatically return to normal operation once the solar irradiance increases to a normal level.
  • J
    Jesus GonzalezAug 26, 2025
    What to do if my Sofar Inverter displays a PVOVP error?
    • C
      Carmen DavisAug 26, 2025
      If your Sofar Inverter shows a PVOVP error, check if too many PV modules are connected in series in a PV string, causing the voltage (Voc) of the PV string to exceed the inverter's maximum input voltage. If this is the case, adjust the number of series-connected PV modules to decrease the voltage of the PV string to fit within the inverter's input voltage range. The inverter should automatically return to normal operation after these adjustments.
  • A
    Abigail RobinsonAug 27, 2025
    What to do if my Sofar Inverter displays a PVUVP error?
    • E
      Elaine MartinAug 28, 2025
      If your Sofar Inverter displays a PVUVP error, check if too few PV modules are connected in series in a PV string, causing the voltage (Vmp) of the PV string to be lower than the inverter's minimum operating voltage. If this is the case, adjust the number of series-connected PV modules to increase the voltage of the PV string to fit the inverter's input voltage range. The inverter should automatically return to normal operation after these adjustments.
  • C
    Christine AndersonAug 30, 2025
    How to fix OverTempFault_Inv error on Sofar 1100TL Inverter?
    • A
      Adam BakerAug 30, 2025
      If your Sofar Inverter shows a OverTempFault_Inv error, ensure that the installation position and method meet the requirements. Check if the ambient temperature at the installation position exceeds the upper limit. If it does, improve ventilation to lower the temperature.
  • J
    John JacksonSep 2, 2025
    How to resolve OverTempDerating error on Sofar 1100TL Inverter?
    • A
      alexander30Sep 2, 2025
      If your Sofar Inverter shows a OverTempDerating error, ensure the installation position and installation method meet the requirements. Check whether the ambient temperature of the installation position exceeds the upper limit. If yes, improve ventilation to decrease the temperature.
  • M
    Michael MartinSep 4, 2025
    What should I do if my Sofar 1100TL shows a BusOVP error?
    • T
      teresa15Sep 4, 2025
      If your Sofar Inverter displays a BusOVP error, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If not, contact technical support.
  • L
    Latoya NelsonSep 7, 2025
    What to do if my Sofar Inverter shows a DciOCP error?
    • R
      Richard GarrisonSep 7, 2025
      If your Sofar Inverter displays a DciOCP error, check the input mode setting (parallel mode/independent mode). If it’s incorrect, change it. If the input mode is correct, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If not, please contact technical support.
  • M
    melissa62Sep 9, 2025
    What should I do if my Sofar Inverter displays a HwAcOCP error?
    • S
      Samantha ClarkSep 10, 2025
      If your Sofar Inverter shows a HwAcOCP error, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If not, contact technical support.