What to do if my Sofar Inverter shows a GridOVP error?
- AApril DicksonAug 20, 2025
If the Sofar Inverter alarm occurs occasionally, it might be due to temporary electric grid issues; the inverter should return to normal when the grid stabilizes. If the alarm is frequent, verify that the grid voltage/frequency is within the acceptable range. If it is, inspect the AC circuit breaker and AC wiring of the inverter. If the grid voltage/frequency is outside the acceptable range and the AC wiring is correct, and the alarm persists, contact technical support to adjust the over-voltage, under-voltage, over-frequency, and under-frequency protection settings after approval from your local electrical grid operator. The root cause is that the grid voltage is too high.