6
2
1
3
4
5
21 N*m
Connect PE
wire first
Optional PE wire
12 MAN-01-00784-1.3
The inverter can either support 4 wire + PE or 3 wire + PE connection
One-hole, standard barrel,
compression lugs only, 600V
Overcurrent protection for the AC output must be provided by others, see manual for guidance
OR
Connecting AC and Protective Earth (PE)
9
30 - 50 mm
CAUTION!
• For aluminum wires, USE
ONLY aluminum lugs
• For copper wires, USE ONLY
copper tin-plated lugs
15 N*m
10 -11 mm
Max 70 mm
2
PE Wire
Max: 120 mm
2
Max
thickness
7 mm
Max width 33 mm
Ø 10 mm
Heat shrink
insulation
When using a stranded wire, use of
ferrule is at the installer discretion
12 N*m
9 N*m
AC
Blue
Black
Gray
Brown
Yellow/Green
Chassis Ground
Yellow/Green