15
E N
N L
Important
The maximum input voltage that the inverter can tolerate is 16 Volts/32Volts. If the voltage that
is supplied is higher than this, then the inverter will break. In this case the repair costs are not
covered by warranty.
6.4 Temperature protection
If the cooling provided by the fan is insufficient, the temperature protection will be activated. The
inverter will shut down the110/ 230VAC output and the red ‘fault’ indicator will light. Once the
inverter has cooled down sufficiently, it will restart automatically.
6.5 Short-circuit on the output
The inverter will switch off the 110/230VAC output voltage if there is a short-circuit of the output.
During this protection, the red ‘fault’ led will flash slowly. The inverter will restart automatically,
once the problem has been resolved.
6.6 Overload protection
The inverter will shut down the 110/230VAC output if the requested power on the output is higher
than the continuous power of the inverter. The red ‘fault’ indicator will flash slowly. The inverter
will restart automatically, once the problem has been resolved.
Important
The overload protection only works with the maximum power and not with the surge power. If
the surge power of the inverter is exceeded then the inverter will break! In this case the repair
costs are not covered by warranty.
Shut down Auto-restart
12Volt models 15,5Vdc+/-0.5 12.6Vdc+/- 0.2
24Volt models 31Vdc+/- 0.5 25.2Vdc+/- 0.2
48Volt models 62Vdc+/- 0.5 50.4Vdc+/- 0.2