SUPPLYING THE SOM-A-TROL
®
WITH POWER
Bring the (4 wire) high voltage power supply to the top right side of the Som-A-Trol
®
and
connect to the panel disconnect and ground lug. (See Diagram and Installation Drawings.)
All close couple systems are prewired; there is a prewired junction box mounted to the side of
the extractor shell. Inside this pre-wired junction box there will be terminals that are the same
as in the panel. Install conduits from the panel to the pre-wired junction box, pull the motor
wires and control wires through these conduits separately and do your final wire terminations
matching numbers from panel to pre-wired junction box.
REMOTE PUSHBUTTON STATION
Mount the remote pushbutton station, run the conduit from the remote pushbutton station to
the pre-wired junction box or panel then pull the wires from the remote pushbutton station to
the pre-wired junction box and do your final hookups in the pre-wired junction box.
WARNING
Improper connection of the equipment grounding conductor can result in a risk of
electrical shock. An equipment grounding conductor must be run with the both high and low
voltage circuit conductors and connected to the pulper/extractor grounding terminal.