Chapter 5 Function parameter
44
261.
F8.02
Motor overload protection
selection
0: Invalid 1: Enable
1
262.
F8.03
Motor overload protection
gain
0.20 to 10.00
1.00
263.
F8.04
Motor overload pre-alarm
coefficient
50% to 100%
80%
264.
F8.05
Over-voltage stall gain
0 to 100
0
265.
F8.06
Over-voltage stall
protection voltage / energy
consumption brake
voltage
120% to 150%
130%
266.
F8.07
Input phase loss protection
selection
Units digit: Input phase loss
protection selection
0: Invalid 1: Enable
Tens digit: contactor actuation
protection
0: Invalid 1: Enable
11
267.
F8.08
Output phase loss
protection selection
0: Invalid 1: Enable
1
268.
F8.09
Short to ground protection
0: Invalid 1: Valid
1
269.
F8.10
Number of automatic fault
reset
0 to 32767
0
270.
F8.11
Fault DO action selection
during automatic fault
reset
0: OFF
1: ON
0
271.
F8.12
Automatic fault reset
interval
0.1s to 100.0s
1.0s
272.
F8.13
Over-speed detection
value
0.0 to 50.0% (maximum frequency)
20.0%
273.
F8.14
Over-speed detection time
0.0 to 60.0s
1.0s
274.
F8.15
Detection value for too
large speed deviation
0.0 to 50.0% (maximum frequency)
20.0%
275.
F8.16
Detection time for too
large speed deviation
0.0 to 60.0s
5.0s
276.
F8.17
Fault protection action
selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12)
(same as units digit)
Hundred digit: output phase loss
(Err.13) (same as units digit)
Thousand digit: external fault
(Err.15) (same as units digit)
00000