Chapter 5 Function parameter
46
284.
F8.27
Reserved
285.
F8.28
Recovery voltage
judgment time of
momentary power cut
0.00s to 100.00s
0
286.
F8.29
Judgment voltage of
momentary power cut
action
50.0% to 100.0% (standard bus
voltage)
10%
287.
F8.30~
F8.32
Reserved
288.
F8.33
motor temperature sensor
type
0: Invalid; 1: PT100 detect
0
289.
F8.34
motor over heat protection
value
0~200
110
290.
F8.35
motor over heat alma
value
0~200
90
5-1-11.F9 Group - Communication parameter
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
291.
F9.00
Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
292.
F9.01
Data format
0: no parity (8-N-2) 2: odd parity (8-O-1)
1: even parity (8-E-1); 3: no parity (8-N-1)
0
293.
F9.02
This unit address
1-250, 0 for broadcast address
1
294.
F9.03
Response delay
0ms-20ms
2ms
295.
F9.04
Communication
timeout time
0.0 (Invalid); 0.1~60.0s
0.0
296.
F9.05
Data protocol selection
Units digit: MODBUS
0: non-standard MODBUS protocol
1: standard MODBUS protocol
Tens digit: Profibus-DP
0: PP01 format
1: PP02 format
2: PP03 format
3: PP05 format
31
297.
F9.06
Current resolution
0: 0.01A 1: 0.1A
0
298.
F9.07
Communication
card type
0:Modbus communication card
1:Profibus communication card
2:Reserved
3:CAN bus communication card
0