Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-136-
10: Ethernet communication
11: High speed pulse HDIB
12: Pulse train AB
13: EtherCAT/PROFINET/EtherNet IP communication
14: Programmable card
15: Reserved
P00.08
Reference
object of B
frequency
command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination
mode of setting
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max. (A, B)
5: Min. (A, B)
0
P00.10
Set frequency
via keypad
When A and B frequency commands are set by keypad, the
value is the initial digital set value of the VFD frequency.
Setting range: 0.00 Hz–P00.03 (max. output frequency)
50.00Hz
P00.11
Acceleration
time 1
Acceleration time is the time needed for accelerating from
0Hz to max. output frequency (P00.03).
Deceleration time is the time needed from decelerating from
max. output frequency (P00.03) to 0Hz.
The frequency inverter ST600 high-performance
multifunction VFD defines four groups of acceleration and
deceleration time, which can be selected via multi-function
digital input terminals (P05 group). The
acceleration/deceleration time of the VFD is the first group
by default.
Setting range of P00.11 and P00.12: 0.0–3600.0s
Model-
dependent
P00.12
Deceleration
time 1
Model-
dependent
P00.13
Running
direction
0: Run in default direction
1: Run in reverse direction
2: Reverse running is prohibited
0
P00.14
Carrier
frequency setup
Carrier
frequency
Electro magnetic
noise
Noise and leakage
current
Cooling
level
High
LowHigh
Low
High
Low
1kHz
10kHz
15kHz
The relation between the model and carrier frequency is
shown below.
Model-
dependent