DP65 / DP105
13
TROUBLESHOOTING
PROBLEM RESET BUTTON (13) CAUSE REMEDY
Motor does not start,
no ignition
FUNCTION LIGHT
Off
SELF-DIAGNOSIS LIGHT
-
Wrong setting of
room thermostat
or other control
Check correct setting of heater control. If
thermostat, make sure selected temperature is
higher than room temperature
Defective
thermostat or other
control
Contact authorised Spitwater service agent
Fan does not start or
stops during start-up
or heating
Flashing
orange
-
No electrical
current
Check mains
Check proper positioning and functioning of
switch, If incorrect contact authorised
Spitwater service agent
Contact authorised Spitwater service agent
Possible electricity
supply problem
Contact licenced electrician
Fan stops during
start-up or heating
Steady
red
Flashing
orange
Presence of flame
before transformer
ignites
Contact authorised Spitwater service agent
Defective photocell Contact authorised Spitwater service agent
Flashing
red or
flashing
red/green
Defective electrical
motor
Contact authorised Spitwater service agent
Defective electrical
motor bearings
Contact authorised Spitwater service agent
Burned out
condenser
Contact authorised Spitwater service agent
Defective electric
ignitor
Contact authorised Spitwater service agent
Defective flame
control box
Contact authorised Spitwater service agent
Defective photocell Contact authorised Spitwater service agent
Insufficient or no
fuel at burner
Contact authorised Spitwater service agent
Defective solenoid
Defective electric
ignitor
Contact authorised Spitwater service agent
Flashing
orange
Internal error of
electronic device
Contact authorised Spitwater service agent
Fan starts and flame
lights, generating
fumes
Steady
green
-
Insufficient
combustion air
Make sure air inlet and outlet are free
Contact authorised Spitwater service agent
Excess
combustion air
Contact authorised Spitwater service agent
Fuel contaminated
or contains water
Contact authorised Spitwater service agent
Air leaks in fuel
circuit
Check the seals on the ducts and the diesel
filter
Insufficient fuel at
burner
Contact authorised Spitwater service agent
Excess fuel at
burner
Contact authorised Spitwater service agent
Heater does not stop
Steady
green
-
Defective solenoid
seal
Contact authorised Spitwater service agent
If the heater is still not working properly, please contact your nearest authorise Spitwater agent