Technical specifications
General
Vibration monitoring: 1 channel
Shock pulse monitoring: 1 channel
Analog outputs (4): 4 - 20 mA analog signal, selective range, no galvanic separation
Main relay (1): 250 V AC, 5A, 1250 VA
Secondary relays (4): 125 V AC, 1A, 60 VA / 150 V DC, 1A, 30 W
Power supply: 230 V AC, 115 V AC ±10% *
Power consumption: max. 6 VA
Operating temperature range: 0 to 50 °C (32 to 122 °F)
Relative humidity: max. 95%
Altitude: up to 2000 m
Casing: polycarbonate/PVC, IP65
TNC connector: silver plated brass, 10 to 15 μ
Display screen: LCD, 4 x 16 characters, back-lighted
Status display: green, yellow, red LED
Dimensions: 200 x 144 x 77 mm
Weight: 1140 g
Machine Guard MG4-REF11A
* Please note: The type of power supply is selected on ordering. It is factory set and cannot be
changed by the user. Please check the unit label for data.