Water Quality Parameters
UV disinfecon is extremely eecve against microorganisms but only if the UV light can pass
through the water it needs to treat. This means that the quality of your water is very important
in order to ensure complete disinfecon.
Treated water should be tested for at the least the parameters listed below. If the water
exceeds the listed parameters SpringWell strongly recommends that appropriate pretreatment
equipment be installed (equipment required will depend on parameters being treated):
Hardness:
<7 gpg (120 mg/L) if hardness level is 7 gpg or slightly below the
quartz sleeve must be cleaned periodically in order to ensure e-
cient UV penetraon; if above the water must be soened.
Iron (Fe):
<0.3 ppm (0.3 mg/L)
Manganese (Mn):
<0.05 ppm (0.05 mg/L)
Turbidity:
< 1 NTU
Tannins (organics):
<0.1 ppm (0.1 mg/L)
UVT (transmiance):
>85% (Please contact SpringWell if water has a UVT that is less than
80% for pre-treatment recommendaons)
You can have your water tested at a private analycal laboratory or by your local dealer. It is
always recommended to install pre-ltraon of at least 5 microns prior to a UV disinfecon
system.