27
14. Re-instate  fuel  supply  and  switch  on  the
burners to ensure that they fire correctly.
15. After  the  appliance  has  achieved  its  operating
temperature,  with  each  burner  running,  carry
out  a  flue  gas  analysis  for  each  burner.    (See
Fig. 38).
16. Check for smoke and flue draught reading.
Boiler Cooker
Air CO
2
% Air CO
2
%
Setting Setting
9 11.5 5 10
8 11.8 4 10.34
7 11.9 3 10.8
6 12.2 2 11.2
Fig. 36
Fig.38
Fig.37
17. Check and set combustion approximate 
settings:
Fig.40
Fig.39
18. Find the correct position of the air control, 
which gives the highest reading of CO2 within 
the range of the table above without exceeding
a smoke No. 0-1 (Bacharach Scale).  (See 
Figs. 39 & 40)
19. Check the oil supply for leaks from storage 
tanks via oil filter.
20. Check if complete system is working correctly.
21. Make sure specified clearances are adhered 
to.
22. Check flue joints are sealed correctly and that 
no escapes are present.
23. If not satisfied check the trouble shooting 
guide.
Boiler Burner
flue  gas  test
point
Oven  Burner
flue  gas  test
point