26
Fig. 35
Fig. 34
INSTALLATION CHECK LIST
1. Check  all  items  from  packaging  are  removed
from ovens and the shelves are properly fitted.
2. Check that electrical wiring is correct.
3. Check that the boiler and heating system is full
of water and purged of air.
4. Check  that  the  boiler  plate  transport  screws
have  been  removed  and  that  the  plates  are  in
their correct positions.  (See section removal of
transport screw and Fig. 41)
5. Time  switches  and  room  thermostats  must  be
on.
6. Check that all valves in the oil line are open and
that the filter is purged of air.  Check that the fire
valve is open.
7. Turn on the electrical supply and check that any
time  switches  are  on  and  room  thermostats
associated with the cooker are on and calling for
heat.  Burners should now fire.
8. Check  that  the  interstat  connection  has  been
wired directly to a motorised valve.  This is done
by  turning  off  room  thermostats,  time  switches
and  temporarily  linking  terminals  6  &  9.    This
should  bring  on  a  motorised  valve  which  will
then call the boiler.
Note: When  the  interstat  calls;  normally  the
motorised valve will open, but the burner will not
operate as the supply to No.6 will be disabled.
9. Check  temperature  differential  between  flow
and return 11°C (20°F) and adjust pump or by-
pass accordingly.
10. Check heating circuit and balance if necessary.
11. With fuel supply off,  switch on the burners.
12. Complete  the  start  sequence  to  lockout  (8
seconds) for both burners observing the correct
operating functions.
13. Ensure  both  pumps  are  purged  of  air.    Check
pump pressure with a calibrated pressure gauge
and adjust it as necessary.  (See Figs. 36 & 37)
For  further  information  refer  to  100K  and  80K
specification on page 5.
4 Meters Max.