iQ Control Box
01.25.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 13
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Index Min
Value
Max
Value
Description Defaults
Single Dual
31 1 99* Close Learn
Speed
Close Learn Speed is the speed used on power up,
during FIS and aer an obstrucon. The controller
display may indicate either 07 or 09 as a door state
and sll use Close Learn Speed based on the
condions listed prior.
This speed is typically set higher than check speed,
to allow faster door moon when not in the check
zones, but sll slower door moon than normal
operaon.
This parameter sets the target speed seng. Other
parameters like close learn torque and close
acceleraon as well as door properes like fricon,
door length, and door weight aect door speed.
20 20
32 1 99 Close Learn
Torque
Close Learn Torque is the torque used on power up,
during FIS, aer an obstrucon.
This torque must be set to comply with ANSI/
BHMA door force requirements.
This parameter sets the maximum current available
to the motor which is directly proporonal to the
door force. This torque seng is used in
conjuncon with Close Learn Speed.
30 25
33 0 99 Close Startup
Length
Close Startup Length is the percent of door length
in which Close Startup Torque parameter is used.
These parameters are used to overcome fricon
encountered at the begining of close door moon.
This parameter should be set as low as possible to
ensure reliable operaon.
0 0
35 1 99 Close Startup
Torque
Close Startup Torque is the torque used when
entering the closing state (07). It is used for a
congurable door length (determined by the Close
Startup Length parameter). Aer this door length,
the torque seng will revert to the Close Torque.
This torque should be set greater than Close Torque
to ensure that the controller can start door moon,
overcome stac fricon, and avoid obstrucons.
This torque must be set to comply with ANSI/BHMA
door force requirements.
This parameter sets the maximum current available
to the motor which is directly proporonal to the
door force.
35 25
Table 3. Settings (continued)
Table 3 Settings continued next page.