PS161-6 Power Supply
Installation Instructions
Overview: PS161-6 converts a 120VAC / 60Hz input, to a 12VDC or 24VDC nominal output. PS161-6 comes with a power-limited power
distribution module with 8 outputs. Class 1 wiring methods and separation of circuits must be considered when connecting DC power supply to the
Delayed Egress hardware.
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire Marshal
European Conformity
Specifications:
Input:
Voltage: 120V AC, 60HZ
Current: 3.5A AC
Input fuse ratings:5A/250V
Battery fuse ratings: 7.5A/32V
Output:
Voltage: 20.0-26.4V
Total output: 6 amps
Power limit/output: 2 amps/per channel
Outputs: 8 (For Delayed Egress applications: use only 4)
Ripple voltage: 910mV (Filtered and regulated outputs)
Protection: Thermal and short circuit protection with auto reset overload protection.
Battery Backup
Built-in charger for sealed lead acid or gel type batteries
Maximum charge current 1.54 amp
Automatic switch over to stand-by is instantaneous with no interruption
Enclosure Dimensions: 12.5” x 13” x 3.25” (3.18mm x 330.2mm x 82.55mm)
Fire Alarm Disconnect:
Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision
AC fail supervision (form “C” contacts).
Visual Indicators
Green AC Power LED indicates 120VAC present.
Additional Features
Short circuit and overload protection.
Unit is complete with power supply, enclosure, battery leads and cam lock.
Enclosure Dimensions
12.5” x 13” x 3.25” (318mm x 330.2mm x 82.55mm)
Question and Answer IconNeed help?

Do you have a question about the Stanley PS161-6 and is the answer not in the manual?

Stanley PS161-6 Specifications

General IconGeneral
BrandStanley
ModelPS161-6
CategoryPower Supply
LanguageEnglish

Summary

UL Listings

UL Listings for US Installations

Lists UL certifications for US installations, including Access Control, Burglar Alarms, and Fire Protective Signaling.

UL Listings for Canadian Installations

Lists ULC certifications for Canadian installations for Burglar Alarm Systems and Access Control.

Product Specifications Overview

Input Specifications

Details voltage, current, and fuse ratings for the power supply input.

Output Specifications

Details voltage, total output current, power limit, and number of outputs.

Battery Backup and Protection

Describes battery backup, charger, thermal/short circuit protection, and overload protection.

Fire Alarm Disconnect and Supervision

Explains the supervised fire alarm disconnect and AC fail supervision features.

Visual Indicators and Additional Features

Covers visual indicators like the AC Power LED and additional features like overload protection.

Installation Instructions

Mounting, Grounding, and Voltage Setup

Guidance on mounting the unit, securing to earth ground, and setting the DC output voltage.

Wiring and Connection Procedures

Instructions for connecting AC power, DC outputs, and delayed egress devices.

Critical Installation Notes

Important notes on EOL resistors, battery types, and FACP integration for proper installation.

Maintenance and Diagnostics

Output Voltage and Battery Testing

Procedures for testing output voltage and battery charge under normal operating conditions.

LED Indicators and Terminal Functions

Explanation of LED diagnostics and identification of power supply/charger terminals.

Terminal Identification and Battery Warnings

Power Distribution Module Terminals

Identifies terminals on the power distribution module and their specific functions.

Stand-by Battery Trouble Indications

Details the circuit for annunciation of battery trouble conditions using relay contacts.

Power Distribution Module Details

Wiring Diagrams and Battery Precautions

NEC Power-Limited Wiring Requirements

Enclosure Dimensions and Template

Appendix A - Compatible Devices

Four (4) Wire Smoke Detectors

Lists compatible four-wire smoke detectors with their standby and alarm current ratings.

Relays

Lists compatible relays with their model, current rating, and manufacturer.

Related product manuals