32 | Stavoklima s.r.o. | www.stavoklima.cz | DITRONIC-MANUAL
FAN CONTROL BY OUTDOOR TEMPERATURE
If activated, this function can control the fan speeds by outdoor
temperature.
This feature may be enabled only when door
contact and outdoor sensor are enabled.
In default the following limit temperatures are congured
for switching between the fan speeds:
0% ÷ 20% 10°C
20% ÷ 40% 5°C
40% ÷ 60% -5°C
60% ÷ 80% -7°C
80% ÷ 100% -10°C
Fan control
by OT
OFF
Fan control
by OT
ON
5
2 1
4 3
LIMIT TEMPERATURES FOR SWIT
CHING BETWEEN THE FAN SPEEDS
Temperatures at which each fan speeds are
switched can be congured manually. Active
only if the fan control by outdoor tem-
perature is set to ON.
100
95
75 65
85
LIMIT TEMPERATURES FOR TRANSI
TION BETWEEN FAN SPEEDS
The limit temperatures for transition of fans
to higher or lower revolution speeds may
be user-dened. For example for EC motors,
when speed 5 is congured, the limit tem-
perature = –10°C and fan revolutions =
100%, which means that if –10°C or less is
outputted from the outdoor sensor, the unit
fans will rotate at 100% (depending on the
door contact, rundown, and more).
-10 °C
LIMIT TEMPERATURE FOR SWIT
CHING THE FAN TO 100% REVS
SPEED EC
Manual conguration of outdoor temperature
at which fan 100% revs speed (EC version)
switches on automatically. The procedure for
conguration of the outdoor temperatures for switching
is identical.
40 20
80 60
DITRONIC-MANUAL
En