PERFORMANCE CURVE
Congured is the dierence of the tempera-
ture required/real when the apparatus runs
at 100% performance. 5°C (default)
EXAMPLE 1:
Performance curve dT = 5°C, real temperature 15°C, required temperature 20°C
Output = request for performance of the outdoor unit 100% = 10V
Output = request for HEAT UP mode = terminals heat up/cool down SWITCHE
EXAMPLE 2:
Performance curve dT = 5°C, real temperature 25°C, required temperature 20°C
Output = request for performance of the outdoor unit 100% = 10V
Output = request for COOL DOWN mode = terminals heat up/cool down NOT SWITCHE
5 °C
SWITCHING HYSTERESIS
A dead zone from the required temperature
when the apparatus neither heats up nor
cools down is determined by the hysteresis.
Range 0.5°C – 3.0°C.
1°C (default)
EXAMPLE 1:
Hysteresis 1°C
Real temperature 20°C, required temperature 20°C, switching of heating
up/cooling down occurs again at 19°C/21°C
EXAMPLE 2:
Hysteresis 2,5°C
Real temperature 20°C, required temperature 20°C, switching of heating
up/cooling down occurs again at 17.5°C/22.5°C
1 °C
BEHAVIOUR OF THE UNIT
IN COOLING DOWN MODE
Eco1: the air curtain cools down only
when door is closed, fans
at 33%
Eco2: the air curtain cools down only
when door is closed, fans at 66%
Comfort: the air curtain cools down when door is closed, fans at 66%
the air curtain cools down when door is open, fans at 100%
ECO2
En
DITRONIC-MANUAL
(default)