OTHER SETTINGS
You can set other parameters here.
RETAIN LOWEST TEMPERATURE
OF OUTLET SENSOR
The controller can retain the lowest tempera-
ture achieved at the outlet sensor.
This data is used as information about medium
temperature. For most customers this informa-
tion can demonstrate that the heat exchanger has frozen.
18.0 °C
FAN CONTROL SETTING BY OUTDOOR
TEMPERATURE
Activation of the fan control by outdoor tem-
perature and setting of the limit temperatures
for switching between levels.
After service code is entered
"2345"
ANTI-FROST PROTECTION (AFP)
AFP o (for the heat exchanger* and the room)
*applies to hot water version only.
Anti-frost
protection ON
Anti-frost
protection OFF
FAN OPERATION AT ANTI-FROST PROTECTION
SELECTION (AFP)
This function enables control of the condition that occurs when
AFP temperature is achieved. OFF = valve is full open and the
fan is o. ON = valve is full open and the fan operates without
change according to the controller. The function is active if the
controller is not in the level 2 of the anti-frost protection. The AFP
does never run in the level 2 to eliminate further drop. Recommendation:
Always select OFF if the air curtain is used for heating as well (balances sud
-
den thermal losses).
Fan at AFP
is OFF
Fan at AFP
is ON
RESTRICTING THERMOSTAT ENABLE
When the set temperature is achieved (outdoor or additional
interior temperature), this function may be used to restrict the
air curtain (fan and heating or heating only). Function type
selection, see . The contact can be used to turn (restrict)
o the heating based on equithermal control.
Restricting
thermostat
OFF
Restricting
thermostat
ON