EF315_r5.1(v12.22) – 03/2023 page 12
CONFIGURATION PARAMETERS
In this section are listed all configuration parameters.
It is advisable to fill the last column with the values set for the application.
PAR. DESCRIPTION
MIN
VALUE
MAX
VALUE
DEFAULT
VALUE
SET
VALUE
P01
Operation Pump 1
(pH)
0 = ON-OFF
1 = Proportional
0 1 0
P02
Dosage direction
Pump 1 (pH)
0 = Acidification
1 = Alkalization
0 1 0
P03 Threshold (desired value) Pump 1 (pH) 5.00 pH 8.00 pH 7.40 pH
P04
Hysteresis (no intervention value or proportional band)
Pump 1 (pH)
0.05 pH 2.00 pH 0.40 pH
P05
Frequency (magnet) or Percentage (peristaltic)
Pump 1 (pH)
2 i/m
5 %
150 i/m
100 %
100 i/m
100 %
P06 Max Dosing Time Pump 1 (pH) (h : min) 0:00 9:59 1:00
P07
OFF Status
Pump 1 (pH)
Weight 1 = Level 1 failed
Weight 2 = Level 2 failed
Weight 4 = Flow/Consent missing
Weight 8 = Maintenance required
0 15 15
P08
Operation Pump 2
(chlorine)
0 = ON-OFF
1 = Proportional
0 1 1
P09
Dosage direction
Pump 2 (chlorine)
0 = De-chlorination
1 = Chlorination
0 1 1
P10 Threshold (desired value) Pump 2 (chlorine)
0 mV
0.00 Cl
2
1000 mV
10.00 Cl
2
680 mV
1.00 Cl
2
P11
Hysteresis (no intervention value or proportional band)
Pump 2 (chlorine)
5 mV
0.05 Cl
2
50 mV
0.50 Cl
2
40 mV
0.40 Cl
2
P12
Frequency (magnet) or Percentage (peristaltic)
Pump 2 (chlorine)
2 i/m
5 %
150 i/m
100 %
100 i/m
100 %
P13 Max Dosing Time Pump 2 (chlorine) (h : min) 0:00 9:59 2:00
P14
OFF Status
Pump 2 (chlorine)
Weight 1 = Level 1 failed
Weight 2 = Level 2 failed
Weight 4 = Flow/Consent missing
Weight 8 = Maintenance required
0 15 15
P15 Start-up Delay (min : sec) 00:10 59:59 00:10
P16 Delay after restoring Flow/Consent (min : sec) 00:00 59:59 00:05
P17 Chlorin. Delay at Start-up for pH Stabiliz. (min : sec) 00:00 59:59 01:00
P18 Chlorine calibration delay (minutes) 5 240
15 (RX)
120 (CAC)
P19
Alarm Relay
Configuration
0 = NO (contact closed = alarm)
1 = NC (contact open = alarm)
0 1 1
P20
FLOW Input
Configuration
0 = NO (input open = OK)
1 = NC (input closed = OK)
0 1 0
P21
EXT.CONS. Input
Configuration
0 = NO (input open = OK)
1 = NC (input closed = OK)
0 1 0
P22 Working Temperature without PT100 0°C 100°C 27°C
P23 Password for Standard Configuration 0 999 0
P24 Password for Advanced Configuration 0 999 0
P25 Language (0 = ITA, 1 = ENG, 2 = FRA, 3 = ESP) 0 3 0