Parameter Value Description
18-3 id.5 75 degree F. Idle set point
Advance key
18-4 h.hy 3.0 degree F. Heat hysteresis
Advance key reads 3 on display
18-5 o.SP 0.0% Open loop set point
Advance key
Step 19: Pressing the advance key at parameter o.SP will advance you back to parameter C.r7
Press the infinity key once to return you to operations Loop menu. Press the infinity
key again to return you to the Home Page.
Step 20: Enter the Factory Page by pressing the advance key and infinity keys together
and holding them for six (6) seconds. CUSt will be in the upper display and
FCty will be in the lower display.
Factory Page
Step 21: Once CUSt is in the upper display and FCty is in the lower display, you are
in the Factory menu. If not, press the infinity key to return to the Home Page
and redo step 20.
Step 22: Press the advance key if CUSt is in the upper display and FCty is in the
lower display. The upper display will now read 1 and the lower display
will read CUSt . Press the advance key again.
Step 23: The upper display will read AC.Pu and the lower display will read PAr .
If the upper display does not read this way, use the up and down keys to change
the value. Once the value has been changed, press the infinity key once.
Step 24: The upper display will read 1 and the lower display will read CUSt . Use
the up or down keys to change the upper display to read 2 , press the advance
key.
Step 25: The upper display will read AC.SP and the lower display will read PAr . If
the upper display reads differently, use the up or down keys to change it to
AC.SP Once complete, press the infinity key once.
Step 26: The upper display will read 2 and the lower display will read CUSt . Use
the up or down keys to change the upper display to read 3 . Press the advance
key once.
Step 27: The upper display will read some parameter or other, and the lower display
will read PAr , Use the up or down keys to change the upper display to read
none.
Once complete, press the infinity key.