INSTALLATION
Specication
36 | WPL E | WPL cool www.stiebel-eltron.com
18.4 Data table
The output data refers to new appliances with clean heat exchangers.
The power consumption of the integral auxiliary drives represents the maximum value and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output data for the appliance (to EN 14511).
WPL 13 E WPL 13
cool
WPL 18 E WPL 18
cool
WPL 23 E WPL 23
cool
227756 223400 227757 223401 227758 223402
Heating output
Heating output at A10/W35 (EN 14511) kW 9.5 9.5 13.4 13.4 18.5
Heating output at A7/W35 (EN 14511) kW 8.93 9.01 12.9 12.9 16.56 14.45
Heating output at A2/W35 (EN 14511) kW 8.09 8.1 11.3 11.3 15.73 14.14
Heating output at A-7/W35 (EN 14511) kW 6.77 6.6 9.72 9.72 13.21 12.27
Max. heating output in silent mode at A-7/W35 kW 6.27 6.27 9.23 9.23 12.55 11.65
Cooling capacity at A35/W20 kW 9.7 13.5 15.8
Cooling capacity at A35/W7 kW 6.7 9.2 12.5
Power consumption
Power consumption at A10/W35 (EN 14511) kW 2.1 2.1 2.9 2.9 4.15
Power consumption at A7/W35 (EN 14511) kW 2.05 2.05 2.89 2.89 4.15 4.10
Power consumption at A2/W35 (EN 14511) kW 2.15 2.15 3.03 3.03 4.35 4.38
Power consumption at A-7/W35 (EN 14511) kW 2.11 2.11 2.97 2.97 4.21 4.21
Power consumption, cooling at A35/W20 kW 3.3 4.5 7.2
Power consumption, cooling at A35/W7 kW 2.8 3.9 5.9
Max. power consumption, fan heating kW 0.29 0.29 0.29 0.29 0.29 0.29
Power consumption, emergency/booster heater kW 8.8 8.8 8.8 8.8 8.8 8.8
Coefficient of performance
COP at A10/W35 (EN 14511) 4.5 4.5 4.6 4.6 4.4
COP at A7/W35 (EN 14511) 4.35 4.35 4.46 4.46 3.99 3.52
COP at A2/W35 (EN 14511) 3.76 3.4 3.73 3.7 3.62 3.23
COP at A-7/W35 (EN 14511) 3.2 3.2 3.27 3.27 3.14 2.91
Cooling capacity factor at A35/W20 2.9 3 2.5
Cooling capacity factor at A35/W7 2.4 2.4 2.1
Sound emission data
Sound power level outdoor installation (EN 12102) dB(A) 62 62 65 65 65 65
Max. sound power level, outdoor installation, silent mode dB(A) 60 60 63 63 63 63
Sound power level for indoor installation (EN 12102) dB(A) 56 56 57 57 58 58
Sound power level for indoor installation, air intake/discharge (EN 12102) dB(A) 61 61 61 61 61 61
Sound pressure level at 1 m distance in a free field dB(A) 53 53 53 53 53 53
Sound pressure level at 5 m distance in a free field dB(A) 39 39 39 39 39 39
Sound pressure level at 10 m distance in a free field dB(A) 33 33 33 33 33 34
Application limits
Min. application limit, heat source °C -20 -20 -20 -20 -20 -20
Max. application limit, heat source °C 40 40 40 40 40 40
Application limit cooling heat source min. °C 20 20 20
Application limit cooling heat source max. °C 40 40 40
Min. application limit on the heating side °C 15 15 15 15 15 15
Max. application limit on the heating side °C 60 60 60 60 60 60
Min. application limit - cooling on the heating side °C 7 7
Max. application limit cooling on the heating side °C 25 25
Application limit cooling on the heating side 35°C °C 20
Application limit cooling on the heating side 40°C °C 12
Energy data
Energy efficiency class A+/A++ A+/A+ A+/A++ A+/A++ A+/A+ A+/A+
■------