 Defrosting control circuit 1
Para-
meter
Description of function
Setting range
Values
default

Assignment of evaporation sensors
(defrosting sensors)
detailed description of sensors in parameters

through

0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from
F1 and F2
2

Defrosting interval
0: no automatic defrosting
1...99 hrs.
8

Type of defrosting
0: no defrosting
1: compressor off only (circulating air)
2: electrical
3: with hot gas
2

Stop at defrosting temperature
0 ... +30.0°C
10.0

Defrosting time limitation
1...99 min.
30

Display of cold store temperature during
defrosting
0: normal
1: last temperature before defrosting
1

Temperature difference to cold store setpoint
in previous cooling
-15°C ... 0.0°C
0.0

Time limitation in previous cooling
1 ... 180 min.
10

Delay of start of defrosting after compressor
off

=2
0 ... 900 sec.
60

Dripping time
0 ... 15 min.
1

Stop delay drip tray heating
0 ... 60 min.
10

Password of parameter level

-99 ... 999 0
 Fan control circuit 1
Para-
meter
Description of function
Setting range
Values
default

Fan speed control mode, Set1
0 ... 100% 80.0

Fan speed defrosting, Set1
0 ... 100% 80.0

Fan speed control mode, Set2
0 ... 100%

Fan speed defrosting, Set2
0 ... 100% 100

Start-up time
0 ... 60 sec.
5

Minimum speed
(output variable if result=0)
0 ... 100% 10.0