19
COH
Overheated condenser alarm
Solutions:
- check the condenser temperature
- check the value of parameter C6.
Main consequences:
- the condenser fan will be turned on.
CSd
Blocked condenser alarm
Solutions:
- check the condenser temperature
- check the value of parameter C7.
- unplug the device and clean the condenser.
Main consequences:
- if the error occurs during the stand-by, it won't be possible to select nor to start any
working cycle
- if the error occurs during a working cycle, the cycle will be interrupted.
ESt
Setting parameters download not completed alarm
Solutions:
- press and release a key to reset the normal visualization
- download again the setting parameters.
Main consequences:
- the device keeps working normally.
CEr
Alarm for the firmware of the setting parameters in EVKEY different from the device one.
Solutions:
- suspend the power of the device
- check that the firmware of the setting parameters in EVKEY corresponds with the
one of the device.
- download again the setting parameters.
Main consequences:
- the device keeps working normally.
Erd
Setting parameters upload not completed alarm
Solutions:
- reset the default settings
- upload again the setting parameters.
Main consequences:
- the digital output will be deactivated.