35
DEX HEATED REGENERATIVE DRYER
Section 6
TROUBLESHOOTING
Symptom Probable Cause Remedy
High humidity alarm (with 
optional dew point monitor)
The regeneration of the desiccant 
beds is insufficient.
Reset the alarm with the “Alarm Reset” 
push button. Verify the heating and cooling 
operations by observing regenerations. Are 
the regeneration temperatures in 
accordance with those listed in Section 3.7? 
The dewpoint probe service valves 
are closed.
Open the probe service valves.
Loss of power alarm The control circuit fuse has blown. Check the fuse and replace if necessary.
The PLC has failed or is in an 
alarm condition.
Check the PLC to verify if any outputs are 
“on” or if the PLC alarm LED is on. Replace 
the PLC if necessary.
The system incoming power has 
been lost.
Check the incoming power and restore the 
supply.
Blower overload alarm The motor overload has operated. Check the motor overload to see if it is 
defective. Check the operating conditions to 
see if the motor is operating overloaded as 
a result of a problem with the blower or 
motor bearing, etc.
Vessel #1 De-pressurization 
failure
The depressurization valve did not 
open.
Check the solenoid valves  for correct 
operation. Check the valve actuator for 
correct operation.
Vessel did not depressurize. Check if the depressurization muffler is 
plugged.
Vessel depressurized but alarm is 
on.
Check pressure switch  for correct 
operation.
Vessel #2 De-pressurization 
failure
The depressurization valve did not 
open.
Check the solenoid valve  for correct 
operation. Check the  valve actuator for 
correct operation.
Vessel did not depressurize. Check if the depressurization muffle is 
plugged.
Vessel depressurized but alarm is 
on.
Check pressure switch   for correct 
operation.
Vessel #1 Re-pressurization 
failure
The repressurization valve did not 
open.
Check the air actuated ball valve for correct 
operation. Check the valve actuator for 
correct operation and check the pilot 
solenoid valve.
Vessel re-pressurized but the 
alarm is on.
Check pressure switch PSH-1 for correct 
operation.